6.1.2
read the mode, NORMAL or 2330 (see the unit respectively).
A connection cable (with crocodile clips and tab terminals) is
attached and can be used when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector into 3314 (SA & SB terminals) or when
required, use the connection cable.
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write: Press "WRITE" and "READ" at the same time to
select the mode and/or write the address. Press "WRITE" and
wait for a beep. ("READ" again as a check.)
3390 Label holder.
To be mounted on the analog base 3312
Intended for a label with "zone-address", "technical address",
etc. to be read also when the detector is plugged in its base. 100
label holders per packet. Excl. labels.
3391 Labels for 3390. Packet with self-adhesive white labels for
label holder 3390. 10 A4-sheets à 132 labels for laser printer
usage. The print-out is done via Win128.

Addressable I/O units

3361 Addressable multipurpose I/O unit.
COM loop. Up to 16 I/O units 3361 can be used.
The unit has two programmable inputs:
Monitored input
....used as zone line input (Z): End-of-line capacitor 470 nF
mounted in the last unit on the line. A short circuit can activate
fault or fire alarm (set via Win128). This input is intended for
conventional detectors.
used as general input (In0):
contacts (set via Win128).
Isolated input (In1): An optocoupler input (external 24 V DC
/ 8 mA is required). Normally low or high (set via Win128).
41
Some units have flying leads for easier connection. After use they might
be disconnected and thrown away.
42
Also in the enclosed analog heat detector 3309.
43
The same physical unit (3361) is also used for the Australian Fan control
function and has a separate dialog box in Win128.
44
It is via Win128 possible to define this input functioning like a manual call
point ("Used as MCP"), i.e. it will not be collectively disabled via menu
"Disable zone, H2/B1", can not be included in two-unit dependence, it can
not use the "alarm delay" function and it can not be disabled via a time
channel.
EBL128 Planning Instructions V1.1.x
41
43
Power supplied via the
44
An input for NC or NO
38
42
.