Overview; The Ft1020G3 System; Printer; Expansion Boards - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

2

Overview

2.1

The FT1020G3 system

FT1020G3 is a microprocessor controlled intelligent fire alarm system, intended for
Analogue addressable smoke detectors, as well as conventional detectors and manual call
points.
Programmable control outputs and output units are available.
addresses can be connected to each Control Unit (CIE). Figure 1 presents an overview of
the FT1020G3 System.
FT1020G3 is available in several types, versions and configurations. It can be used as
stand-alone Control Unit or connected to a TLON network, i.e. in a "system" with up to 30
Control Units. Each Control Unit has access to all information.
FT1020G3 is designed and assessed to the Australian Standard AS7240.2, AS7240.4 and
NZS4512:2010. The Fire Brigade Panel controls and indicators are incorporated as part of
the faceplate and conform to AS4428.3:2010.
2.1.1

Printer

The Control Unit FT1020G3 can be fitted with an optional printer
2.1.2

Expansion boards

Up to six expansion boards can be mounted in FT1020G3 CIE. The following expansion
board types are available:
Product type no.
4580
4581
4583
For more details, refer to chapter "Expansion boards 458x", page 24 and drawings F728,
F729 and F731.
2.1.3

Power supply

The primary power source is a switch mode power supply, 230 V
Watt).
The standby power source is a backup batteries (2 x 12 V). In the standard cabinet, up to
24 Ah batteries can be fitted. Larger batteries (up to 65 Ah) require additional battery box.
The batteries and the switch mode power supply are connected to the Main board (5010).
See chapter "Power supply", page 177 for more information.
2.2

Software (S/W) versions

Due to continual development and improvement, S/W versions are being updated from
time to time. When a new FT1020G3 Control Unit is required to be installed in a network
system with "older" Control Units, the software in the older Control Units must be updated
(or download an older version in the new Control Unit). The S/W version must be the
same in all Control Units in a TLON network.
1
Printer 5058 is a spare part for the FT1020G3 with a printer, i.e. it comes without a mounting frame etc.
Product name
8 zones expansion board
8 relay outputs expansion board
Inputs and outputs expansion board
10
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Up to 1020
1
.
/ 24 V
, 6.5 A (150
AC
DC

Advertisement