Gaseous extinguishing system control module

6.5.1

Overview

The gaseous extinguishing system control module is provided for use as an option in
FT1020G3. The module comprises the following:
Control Board (SUB928) with software for CIE interface.
Display Board (SUB929)
CIE interface board (SUB943).
Front panel decal with interconnection cable
The gaseous extinguishing system provides outputs to the following Brooks gas ancillary
equipment:
A series of Brooks Warning Signs
Brooks Local Control Station (LCS)
Voice / Tone Electronic Sounder
Dual Strobe Module
The control module combined with other Brooks system components is designed to provide
the monitoring and control functions of a complete gaseous extinguishing system that
meets the requirements of the relevant clauses 7.1 to 7.6 of the Australian Standard
AS4214-2002 (including amendment 1). For more details, refer to FT2GAS Operation /
technical manual MA400.
The control module provides the following inputs / outputs:
Fully supervised gas release 24V
Fully supervised input circuits e.g. gas lock-off valve input, manual release input
and gas discharged sensor input.
Fully supervised system warning sign 24V
Fully supervised 2 wire system output 24V
warning signs (alarm 1 [+/-] & alarm 2 [-/+]) rated @ 3A maximum.
Gas release clean-contact relay output rated @ 2A maximum.
Gas Fault clean-contact relay output rated @ 2A maximum.
Gas Isolate clean-contact relay output rated @ 2A maximum.
Four-wire interface for Local Control Station (LCS). Both the local gas isolate
control and the local gas release control are fully supervised for open and short
circuit faults.
Adjustable gas release timer, set via a built-in DIP switch.
Note: the current rating above is the maximum current capacity of the outputs, a power
supply and battery calculations must be performed to ensure that the power supply
capacity is sufficient to run the system in full alarm condition without exceeding the
maximum current rating of the power supply. The gas module might need a separate
power supply with PSU supervision board and backup batteries
6.5.2
Display board (SUB929) & decal
The front decal of the gaseous extinguishing system is shown in Figure 22 below. The
display board SUB929 is mounted on the inner door behind the front decal.
Technical/Programming Manual
output rated @ 5A maximum.
DC
output rated @ 0.5A maximum.
DC
for level 1 and level 2 alarm to Brooks
DC
46
FT1020G3 Rev 2.2.1