Output Signal Periods - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Level, alarm: Level, default 58° C.
Note: Changing these parameters will affect the sensitivity and detection time and should
be done by authorised personnel only! In addition, a special password is required to
change the fire alarm parameters.
22.3.4

Output Signal Periods

See also chapter "Output signal period", page 84.
To open the output signal period dialog box as shown above, go to the EBLWin menu
System | Output Signal Periods...
In the list (above), Steady (continuously) and Intermittent 0.8 / 0.8 s are already defined
since these alternatives are often used. It is however, possible to define them to something
else.
User defined 1-8 have to be defined individually:
Name: Normally changed to something that describes the output signal (e.g. "Steady") or
what it is meant for (e.g. "Alarm devices").
Type:
Depending on the selected type, one or more of the following fields might have to be filled-
in.
Delay time: Can be set to 0-255 x 0.8 = 0 - 204 sec.
Pulse length: Can be set to 0-255 x 0.8 = 0 - 204 sec.
Steady / continuous (default)
Intermittent
Pulse
Steady, delayed activation
Intermittent, delayed activation
Pulse, delayed activation
Steady, delayed de-activation.
156
Technical/Programming Manual
FT1020G3 Rev 2.2.1