the COM loop will now be identified and listed in EBLWin i.e. the SSD will be auto generated
with default settings for all units (01-01, 01-02, 01-03, etc.). The SSD can be edited, saved
before the download can take place. Repeat the same procedures for every other Com
loop. The SSD can now be downloaded (see below) to FT1020G3 directly.
23.2

SSD Download

23.2.1

SSD Download to Single Control Unit

Start the SSD download from EBLWin. A text message will be shown in the Control Unit
display: "Downloading SSD".
When the download is completed the Control Unit will restart. After the restart another text
message will be shown in the display:
Code 25 indicates a normal restart after the SSD download. Acknowledge the restart fault.
If the download was unsuccessful, another fault will be generated.
This text message means that the SSD file has not been downloaded successfully, i.e. a
new download has to be performed.
23.2.2

SSD Download to Control Units in a TLON Network

The SSD for all Control Units can be downloaded via a PC / EBLWin, connected to one
Control Unit. The download will be performed to the Control Units, one at a time, according
to chapter "Single Control Unit" above. The download is performed in a consecutive order,
i.e. 0-1-2-3-4-......-29 amongst the selected Control Units but the Control Unit where the
PC is connected will automatically be the last one to get the SSD downloaded.
When the SSD download to a Control Unit is completed, that Control Unit will automatically
restart and generate a restart fault.
23.3

User definable text messages download

Each alarm point, zone and zone line input can have a unique user definable alarm text
programmed via EBLWin. When a fire alarm is activated (e.g. an addressable alarm point),
the presentation number (Zone - Address) will be shown in the Control Unit and in
1728/1736 display together with its user definable alarm text.
All alarm texts, up to 40 alphanumeric characters each, are created and downloaded
(included in the site specific data – SSD) via EBLWin.
When a printer is available the alarm text will be printed with the presentation number.
A Fault message for an alarm point, zone or zone line input will also show the text message.
160
Each unit have to be running i.e. be connected, power supplied and the address, mode etc. have to be set. NOTE: During this
check, the COM loop will be disconnected (disabled) and no alarms or faults can be activated. Disconnected COM loop is
indicated by the LED "Disablements" (L8).
FAULT: Restart Control Unit nn, code 25
DD-MM-YYYY
HH:MM
FAULT: Site specific data (SSD), CU nn
DD-MM-YYYY HH:MM