Operating Instructions Fire alarm system EBL512, V2.7.x

Door open

A special key is used to open the control unit door to get access to the
front / system, see chapter "Access levels", page 23. The same type of
key is also used to open the ext. FBP door. Door open is indicated by
LED "Door open" (L10)
open" tab), the following can be programmed (default settings shown):

LED "Door open"

Indication door open affected by
 Door in any control unit or any external FBP: Door open in a
C.U. is indicated by LED "Door open" in all C.U:s and in all ext.
FBPs. Door open in an ext. FBP is indicated by LED "Door
open" in all C.U:s and in all ext. FBPs.
 Door in any control unit: Door open in a C.U. is indicated by
LED "Door open" in all C.U:s and in all ext. FBPs. Door open in
an ext. FBP is indicated by LED "Door open" in that ext. FBP
only.
 Door in control unit or external FBP connected to own
control unit: Door open in a C.U. is indicated by LED "Door
open" in that C.U. and all ext. FBPs connected to that C.U. Door
open in an ext. FBP is indicated by LED "Door open" in the C.U.
it is connected to and all ext. FBPs connected to that C.U.
 Door in control unit: Door open in a C.U. is indicated by LED
"Door open" in that C.U. and in all ext. FBPs connected to that
C.U. Door open in an ext. FBP is indicated by LED "Door open"
in that ext. FBP only.
Outputs for routing equipment (Fire
brigade tx and Fault tx)
Disablement of routing equipment
 No disablement: Door open in a C.U. or an ext. FBP will not
disable the output(s) for routing equipment (Fire brigade and fault
tx).
 Disable by door in any control unit: Door open in any C.U.
will disable the output(s) for routing equipment (Fire brigade and
fault tx) in all C.U:s.
 Disable by door in any control unit or any external FBP:
Door open in any C.U. or any ext. FBP will disable the output(s)
for routing equipment (Fire brigade and fault tx) in all C.U:s.
Disabled outputs for routing equipment are indicated by the LED
"Disablements" (L8) and "Fault / Disablements Fire brigade tx"
(L15) and listed in menu H4/U1.