Item
Mains Voltage
System Voltage
Current Consumption
Ambient Temperature (⁰C)
Ambient humidity (%RH)
Cabinet Size (mm)
Enclosure Material
Enclosure Colour
Approvals
Standard Inputs / Outputs
Expansion Boards
I/O Matrix 4582 board
Note: I/o matrix 4582 is now integrated in the new zone control 1205, fan control 1206 and
damper control 1211 modules, same limitations apply. Refer to Chapter 5, page 28.
1
Refer to G3 block wiring diagrams shown in chapter 34, Figure 24 page 176
2
First input I
0
Expansion boards are internally connected to COM loop 0, ensure total number of Expansion Boards and
3
modules with built-in I/O matrix connected to COM loop 0 does not exceed 6.
4
Reduce the number of modules containing 4582 connected to COM loop 0 by one for every Expansion Board
used.
If no Expansion Boards fitted, up to 24 fan/damper control modules can be used i.e. 96 individual fan/damper
5
Specifications
230V
(195-253), 2 A
AC
24V
@ 6.5A
DC
Quiescent / alarm current is calculated by EBLWin and is
dependent on other equipment fitted in FT1020G3, type and
number of expansion boards, connected external equipment, etc.
Operating 0 to + 40, Storage -40 to +70
Maximum 90, non-condensing
Small 19" cabinet 13U, 700H x 600W x 250D
Large 19" cabinet 22U, 1050H x 600W x 250D
Battery box 19" cabinet 6U, 350H x 700W x 250D
1.5 Zinc annealed steel
Oyster, ripple finish
AS7240.2:2018, AS7240.4:2018, AS4428.3:2020 and
NZS4512:2010
Four COM loops (0-3), each loop can connect up to 253 devices
Four programmable non-supervised / supervised inputs (N/O or
N/C) I
-I
2
0
3
Four Programmable Supervised Voltage Outputs, 0.5 Amp each
1
Two Programmable Relay Outputs, contact rating 2 Amp
Two non-programmable relay outputs for ASE (fire & fault)
Six x 24V
outputs for Web server, ASE, Remote Display Units,
DC
external applications 0.5 – 3.15 Amp.
Max. 6 of 4580 or 4581 or a combination
Max. 24, 6 per COM loop if no Expansion Boards on Loop 0
fitted. Up to 6 modules can be used as zone or generic + 18 Fan
Control Modules (4 fans per module)
cannot be used in NZ convention, only 3 programmable inputs are available.
5
15
Operation Manual
FT1020G3 Rev 2.10.4
of both.
3
4

Advertisement