Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Open door

A special key is used to open the control unit door to get access to the
front / system. The same type of key is also used to open the ext. FBP
door.
If any door in the system is open the following symbol is shown in the
display's symbol area:
See also chapter Open doors (H4/U3), page 111.
Outputs for routing equipment (Fire
brigade tx and Fault tx)
Via EBLWin the following can be programmed (default settings
shown):
Disable routing equipment by door switch
 None: Open door in a C.U. or an ext. FBP will not disable the
output(s) for routing equipment (Fire brigade tx and fault tx).
 Any control unit door: Open door in any C.U. will disable the
output(s) for routing equipment (Fire brigade tx and fault tx) in
all C.U:s.
 Any door: Open door in any C.U. or any ext. FBP will disable
the output(s) for routing equipment (Fire brigade tx and fault tx)
in all C.U:s.
Disabled outputs for routing equipment are indicated by the LEDs
Fault / Disablements "General disablements" (L10) and "Fire brigade
tx" (L12) and listed in menu H4/U1.

Silence buzzer with door switch

Via EBLWin can be set that the built-in c.i.e. buzzer will be silenced
when the c.i.e. door is open.