Operating Instructions Fire alarm system EBL512 V2.3.x

"Silence Alarm devices"

In the control unit (on the FBP) there is a push button (P3) "Silence
Alarm devices".
If the push button "Silence Alarm devices" is pressed during a pre-
warning, a fire alarm or a Co-incidence alarm, the following will
happen:
• LEDs "Fire" (L1) and "Alarms queued"
blinking (0.4 / 0.4) to steady ON
• activated outputs
alarm devices), will be turned OFF
In case of a new alarm, or if the push button "Silence Alarm devices"
is pressed again, the sounders will automatically sound again and the
LEDs "Fire" and "Alarms queued" starts blinking.
NOTE! This is also valid for Pre-warning and Co-incidence alarm.

Disable / Re-enable alarm devices

24
The outputs
programmed for sounders (type 3 = alarm devices) can
via menu H2/B9 be collective disabled for one, more or all control
units. This is indicated by LED "Disablements" (L8) and LED Fault /
Disablements "Alarm devices" (L13) steady ON.
In case of a fire, the sounders will remain disabled, i.e. the alarm
devices will not sound.
They will remain disabled until they are re-enabled again via menu
H2/B9.
See also chapter "Disable / Re-enable alarm devices (H2/B9)", page
86.
23
When more than one fire alarm is activated.
24
Including Addressable siren 3377 and Addressable sounder base 3378.
25
24
, programmed for sounders (type 3 =
23
(L2) changes from