31.3
Action
"
"
Menu
Scroll to menu H9.
"
"
Scroll to menu C3.
"
"
Write the area number
and point (e.g. 001 and
01).
"
"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Disable / re-enable interlocking output
(H9/C3)
Interlocking outputs (Type = Interlocking) can be individually
disabled via this menu (and collectively via menu H2/B3).
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. Up to 100 interlocking outputs can be disabled in
the whole system.
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
The LED Fault / Disablements "General disablements" (L10) is also
indicating one or more disabled interlocking outputs.
Text in display
H9 Interlocking outputs and inputs
C1 Activated interlocking outputs / inputs
C2 Activate / deactivate interlocking output
C3 Disable / re-enable interlocking output
C3 Disable / re-enable interlocking output
Disable
Interlocking output area: 000 point: 00
Disable
Interlocking output area: 001 point: 01
-- Re-enable list (1) ---------------------------------------------
Interlocking output area: 001 point: 01
155
Comments
According to chapter
"Access", see page 88.
Via menu C3 can
interlocking outputs be
disabled / re-enabled.
Write area number and
address and press "
to disable, which will be
indicated with "√" and a
beep. The output will
directly be shown in the
Re-enable list.
If the specified output
doesn't exist, it will be
indicated with "X"
instead of "√" and a
beep.
Use the soft key "|" to
toggle between Disable
and Re-enable list.
"