The "Modbusread" Object - Siemens SIMATIC TIM 3V-IE DNP3 System Manual

Industrial remote communication telecontrol
Table of Contents

Advertisement

MODBUS write status
The result of a write job is returned by the MODBUS slave in an acknowledgement message.
The result is returned as a hexadecimal word and can be saved as a status in the input area
of the CPU.
Name:
Memory area:
DB No.:
Address [Byte]: Input field for the byte number in the selected memory area.
Range of val-
ues:
Table 6- 9
Code
0x7002
0x8000
0x8001
0x8002
0x8003
0x8004
0x8005
0x8006
0x8008
0x800C
0x800D
0x800E
0x800F
0x8010
6.6.14.3

The "ModbusRead" object

The "ModbusRead" object
To map the data to be read between the MODBUS slaves and S7 CPU, the "ModbusRead"
object is available. A separate "ModbusRead" object is configured for each MODBUS slave.
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
MODBUS write status
The following options are available for the address range of the S7 CPU:
DB: Data block
Memory bit: Memory bit area
Input: Process input image (PII)
Specifies the DB number in the CPU if the "data block" memory area (DB) was
selected
See following table
Value range of the MODBUS write status
Meaning
Job executed without errors
Job executed with error
Illegal Function
After this error occurs, the S7 address of this write job is no longer read until the
next restart on the TIM.
Illegal Data Address
Illegal Data Value
Slave Device Failure
Message transferred but slave device busy with a different process (Acknowledge)
Slave Device Busy with other process
Memory Parity Error
Wrong CRC check value in the response message of the slave
Wrong net data in the response message of the slave
Wrong slave address in the response message of the slave
After this error occurs, the S7 address of this write job is no longer read until the
next restart on the TIM.
Wrong function code in the response message of the slave
No response (send timeout exceeded)
The SINAUT Configuration Tool
6.6 TD7onTIM
229