Siemens SIMATIC TIM 3V-IE DNP3 System Manual page 193

Industrial remote communication telecontrol
Table of Contents

Advertisement

Assignment of the status byte for operator input
Bit no.
Status
For val-
ue:
Unused bits are set to 0
"Tolerance time for hardware input" box
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
7
6
5
-
-
-
0
0
0
Max. input time
Enter value x 1 [s] (10 corresponds to 10 seconds)
0
Monitoring time for commands entered over hardware inputs, or setpoints
and parameters whose transmission is triggered over a hardware input. If the
1 signal is set at these hardware inputs for longer than defined in Max. input
time, then the "input error" bit is set in the status byte for operator input. Fur-
ther hardware entries are not processed as long as the "input error" bit is set.
The max. input time is specified in seconds.
A time of at least 30 seconds is recommended (entry: 30).
0 (zero) can be entered if the parameter is not required.
Min. Input Time
Enter value x 0.1 [s] (10 corresponds to 1 second)
0
Delay time for commands entered over hardware inputs, or setpoints and
parameters whose transmission is triggered over a hardware input. The
message is entered in the send buffer of the TIM only if the currently entered
command, setpoint for parameter remains unchanged for the specified delay
time and no other command or setpoint input is detected during this time.
The min. input time is specified in tenths of seconds.
A time of at least 1 second is recommended (entry: 10).
0 (zero) can be entered if the parameter is not required.
The SINAUT Configuration Tool
4
3
2
-
-
1-out-of-
n error
0
0
1
6.6 TD7onTIM
1
0
Input
Input OK
error
1
1
193