ERRCLS
ERRCOD
FF
03
FF
04
FF
05
FF
06
FF
07
FF
08
FF
09
FF
20
FF
22
81
04
83
01
84
02
84
04
84
05
85
00
87
02
E0
FF
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
Meaning
Wrong LAN connection: The connection index is higher than the maximum index limit. The
message is deleted.
Wrong LAN connection:
The send channel was not found.
or
The addressed connection does not exist.
The message is deleted.
No memory could be reserved for the send job. The message is deleted.
No memory could be reserved for the send job. The message is deleted.
No send job exists. The message is deleted.
The send job is already being used. The message is deleted.
During the LAN connection establishment, there were still messages in the queue. All mes-
sages in the queue will be deleted.
Only with TD7onTIM: The message is generated when a read or write job is transferred by
TD7onTIM to the LAN COM and no acknowledgement is received from the CPU within 5
seconds. The job is returned with a negative acknowledgement to TD7onTIM by the LAN
COM.
Only with TD7onTIM: The message is generated when a read or write job is transferred by
TD7onTIM to the LAN COM and there is no connection (CR connection) to the local CPU.
The job is returned with a negative acknowledgement to TD7onTIM by the LAN COM.
Context is not supported:
Errors in the PDU structure
or
Service unknown.
No memory can be reserved to forward the received message. The message is acknowl-
edged negatively to the sender with result code 0x8301.
The TIM has sent a message and has received a negative acknowledgement from the partner
with result code 0x8402 (remote BRcv block is in the incorrect status). The message is re-
peated.
A message was received via the LAN but could not be forwarded because there was no re-
ceive job. The message is acknowledged negatively to the sender with result code 0x8404.
The TIM has sent a message and has received a negative acknowledgement from the partner
with result code 0x8405 (remote BRcv block is DISABLED). The message is repeated.
Illegal PDU size:
Received PDU is larger than the negotiated maximum PDU size.
or
The response does not fit in a PDU of the negotiated maximum PDU size.
A message with an unknown RID was received. The message is discarded and acknowl-
edged negatively with event code 0x8702.
Error coding