INTRODUCTION
The Model TBM-2 Termination Block module
from Siemens Industry, Inc., is the central
connection point for audio functions in the
MXLV System (See Figure 1). The ACM-1
Audio Control module communicates with
other modules in the system through the
TBM-2. In addition, the TBM-2 has connections
for the recording of telephone and microphone
messages, and the control connections to
activate recording equipment. Refer to the
CSG-M Manual, P/N 315-090381, to select
the Voice Options for your system.
The TBM-2 has two single pole, double throw
(SPDT) dry contacts, AUX CTRL1 and AUX
CTRL2, that control recording equipment.
When the microphone or telephone is active,
the signal goes to the chosen auxiliary output
and the corresponding control output changes
state. The TBM-2 does not include connectors
or cables for connecting the auxiliary outputs
and auxiliary controls.
The TBM-2 has a connection for an external
signal source. Use the AUX IN input and a
VSM-1 function to connect an external signal
source to the MXLV System. See Figure 4 for
information on input signals.
The TBM-2 provides screw terminal blocks
and connectors that interface the internal
wiring and field wiring (See Table 1).
For additional information on the MXL/MXLV
System, refer to the MXL/MXLV Manual, P/N
315-092036.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-093782-9
TABLE 1
TBM-2 CONNECTIONS
Connector
TB2
Digital Message Unit audio signal
connection
TB5
Supervised riser signals to System
(Style Y or Z)
TB4
Supervised telephone riser signal
(Style Y)
P1
SPDT contact to start the recorder for
AUX OUT 1
P2, P3
Plug-in cable power connections for
ACM-1
P4
Plug-in cable power connection for
VSM-1/VLM-1/VFM-1
P5
Plug-in cable power connections for
TMM-1
P6
SPDT contact to start the recorder for
AUX OUT 2
J1
AUX IN RCA type jack
J2
AUX OUT 1 RCA type jack
J3
AUX OUT 2 RCA type jack
INSTALLATION
Remove all system power before installation,
first battery and then AC. (To power up, connect
the AC first and then the battery.)
The TBM-2 mounts on the right side of the
backbox next to the MMB or PSR-1, approxi-
mately one-third of the way down from the top
(Refer to Figure 2).
NOTE: In a Remote Extender enclosure the
TBM-2 mounts below the PS-5N7. Refer
to the PS-5N7 Instructions, P/N 315-092729.
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
Connects

Advertisement

loading

Summary of Contents for Siemens TBM-2

  • Page 1 AC first and then the battery.) wiring and field wiring (See Table 1). The TBM-2 mounts on the right side of the For additional information on the MXL/MXLV backbox next to the MMB or PSR-1, approxi-...
  • Page 2 • Connect terminals 2 and 3 in another cable coming back from the last destination of 2. Place the TBM-2 assembly face up on the Riser 1. three threaded studs arranged in a triangle with TB5, the 15 position terminal block at •...
  • Page 3 6 or higher, for additional wiring information. DV-100 DV-100 OR DMC-1 OR DMC-1 NO CONNECTIONS TO VSM-1/VLM-1/VFM-1 MODULES POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <50K OHMS FOR TERMINALS 1-14. 4 WIRE CABLE Figure 3 TBM-2 Wiring Diagram (with MMB or PSR)
  • Page 4 8. Refer to Wiring Specification for MXL, MXL-IQ and MXLV properly. Always complete the full system test to Systems, P/N 315-092772 revision 6 or higher, for additional ensure that all applications function completely. wiring information. Figure 4 TBM-2 Wiring Diagram (with PS-5N7 in an Extender Enclosure) P/N 315-093782-9...