The SINAUT Configuration Tool
6.6 TD7onTIM
Parameters of CmdReceive:
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Channel "CmdFeedBack"
Channel type: DNP command response
Returns the value of the output address of the receiving channel "CmdReceive" to the
master.
218
Output mode
• Pulse on
• Latch on/off
Pulse on
Specifies the type of command The control code received from the master is
evaluated.
Max. pulse duration
0 ... 2147483647
0
Monitors the pulse duration sent by the master (On-time). If the pulse dura-
tion received from the master exceeds the value configured here, the com-
mand is rejected.
If you enter 0 (zero), the monitoring is disabled.
Pulse duration equivalent time
0 ... 2147483647
0
Replacement value for the pulse duration If the pulse duration received from
the master exceeds the value configured in "Max pulse duration". The pa-
rameter is only used when "Max. pulse duration" is configured.
If the value is 0 (zero), no replacement value is used.
Number of pulses
0 ... 255
0
Monitors the number of pulses sent by the master (Count). If the number of
pulses received from the master exceeds the value configured here, the
command is rejected.
If you enter 0 (zero), the monitoring is disabled.
System Manual, 12/2015, C79000-G8976-C253-04
TIM DNP3