Siemens SIMATIC TIM 3V-IE DNP3 System Manual page 190

Industrial remote communication telecontrol
Table of Contents

Advertisement

The SINAUT Configuration Tool
6.6 TD7onTIM
PartnerStatus
The optional PartnerStatus object can be used to monitor the reachability of up to 8
communications partners (DNP3 master stations). The status is made available to the CPU
in an output byte. One bit per communications partner is reserved in the output byte to
indicate the status of the partner:
If TD7onTIM has a connection to more than 8 partners whose status needs to be monitored,
the "PartnerStatus" system object needs to be configured more than once.
Image 6-16
Name:
Memory area: The following options are available:
DB No.:
Address
[byte]:
Name:
Explanation:
Bit status:
190
Parameter assignment dialog of the "PartnerStatus" system object
Status output byte
• DB: Data block
• Memory bit: Memory bit area
• Output: Process output image (PIQ)
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Input box for the byte number in the selected memory area
Partner
In the 8 selection boxes, the communications partners to be monitored are
assigned to the 8 status bits of the output byte. The list boxes display only
the partners with which the TIM can actually communicate; in other words, to
which a connection was configured.
Status = 0: Problem on partner or bit not assigned
Status = 1: Partner OK
System Manual, 12/2015, C79000-G8976-C253-04
TIM DNP3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic tim 4r-ie dnp3Tim 3v-ie dnp3Tim 4r-ie dnp3

Table of Contents