Siemens SIMATIC TIM 3V-IE DNP3 System Manual page 294

Industrial remote communication telecontrol
Table of Contents

Advertisement

Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
Event ID
Detailed
Status message
(hex)
event
(hex)
F560
0405
DNP3 data output locked
F360
0405
DNP3 data output released
F560
0406
Unknown control message
F560
0407
Error releasing memory
F560
0408
Time-of-day function not available
F560
0409
WAN SDB cannot be interpreted
F560
040A
Error creating a task
F560
040B
WAN driver successfully installed.
F960
040C
Modem does not set CTS signal
F860
040C
Modem sets CTS signal again
F560
040D
WAN interface disrupted
F460
040D
WAN interface OK
F560
040E
WAN driver ready for communication
F560
040F
Time synchronization received
F560
0410
Unsolicited event transmission activated
or deactivated
F560
0411
IP connection established
F360
0411
IP connection terminated
F560
0412
Inconsistent routing table
F360
0413
DNP3 connection disrupted
F260
0413
DNP3 connection established
F560
0414
Size of the process image of the inputs
F560
0415
Size of the process image of the out-
puts
F560
0416
TD7 data cannot be interpreted
F560
0417
Unknown DNP3 subscriber address
received
F560
0418
Command rejected
F560
0419
Command not supported
F560
0420
Installation abort - DNP3 stack has
detected an inconsistent parameter
assignment.
294
Meaning
No DNP3 communication possible
DNP3 communication possible
Internal error
The available RAM memory on the module is exhausted.
Time-of-day synchronization by DNP3 master station not
possible
Inconsistent system data block
Internal error
DNP3 driver loaded
CTS control signal on the serial interface inactive
CTS control signal on the serial interface active
Serial communication disrupted. Bad data frame, for
example due to incorrect baud rate or invalid parity.
Serial communication is OK again.
WAN driver ready
DNP3 master station has synchronized system time.
Request to activate of deactivate unsolicited messages
Connection to DNP3 master station was established.
Connection to DNP3 master station was terminated.
Inconsistent configuration
Connection to specified master station disrupted
Connection to specified master station established
Highest DNP3 indexes of the input values (received from
DNP3 master station) are output.
Highest DNP3 indexes of the output values (sent to
DNP3 master station) are output.
Internal error
DNP3 master station sends unknown address. The re-
ceived master station and station address are displayed.
A command of the DNP3 master station could not be
executed. Object group, variation and type of the com-
mand are displayed.
An unknown or unsupported command of the DNP3
master station was received. Object group, variation and
type of the command are displayed.
Configuration error
System Manual, 12/2015, C79000-G8976-C253-04
TIM DNP3