● Second scheme:
The number of seconds between synchronization activities can be set in the "Second
scheme" drop-down list.
● Time of day:
Synchronization takes place once a day. Set the time of day for the synchronization in the
"Time of day" drop-down list box (for example 01:00).
On dedicated lines, a synchronization cycle of 1 hour is recommended.
On the DNP3 WAN, the DNP3 master station is the synchronization master.
"Node List" tab
The node list displays all the communications subscribers connected to the current network;
in other words, TIM modules. It also lists the station name, the WAN address and the
configured node type making it easy to check these parameters throughout the network.
The WAN address has no further significance for DNP3.
Image 5-12
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
5.6 Configuring networks and network nodes in STEP 7 / NetPro
Node List tab
Configuration in STEP 7