Meaning Of Errcls And Errcod - Siemens SIMATIC TIM 3V-IE DNP3 System Manual

Industrial remote communication telecontrol
Table of Contents

Advertisement

Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
Event ID
Detailed
Status message
(hex)
event
(hex)
F460
0808
Message queue overflow (outgoing)
F960
0809
CTS error (incoming)
F860
0809
CTS error (outgoing)
F560
080A
UART error (incoming)
F460
080A
UART error (outgoing)
F360
080B
Status change of the MODBUS slave
(incoming)
F260
080B
Status change of the MODBUS slave
(outgoing)
F560
080C
Negative S7 acknowledgement re-
ceived (message only incoming)
F560
080D
Negative S7 access result received
(message only incoming)
7.3.6.5

Meaning of ERRCLS and ERRCOD

Meaning of ERRCLS and ERRCOD in messages 0113 and 080C
Table 7- 6
Meaning of ERRCLS and ERRCOD (hex)
ERRCLS
ERRCOD
FF
01
FF
02
296
Meaning
The LAN connection via which the frame is to be sent is not established. The message is
deleted.
The queue of the LAN connection via which the frame is to be sent has overflowed. The mes-
sage is deleted.
Meaning / remark
Meaning in byte 5 of the diagnostics message:
1 = LAN COM
2 = S7 adapter
3 = Modbus adapter
MODBUS slave not accessible
MODBUS slave accessible
Byte 6 of the message codes the error class (ERRCLS)
and byte 7 codes the error code (ERRCOD). For the
meaning of ERRCLS and ERRCOD, see Meaning of
ERRCLS and ERRCOD (Page 296).
Bytes 6 and 7 of the message code the access result
(hex) with the following meaning:
FF = success
01 = hardware error
02 = temporary lack of resources
03 = object access not permitted
05 = invalid address
06 = type not supported
07 = type inconsistent
0A = object does not exist
0E...EF: Reserved
FE = data unchanged since last access
System Manual, 12/2015, C79000-G8976-C253-04