The SINAUT Configuration Tool
6.4 The connection configuration
The connection with the preferred path should therefore be applied first.
A station always replies on the path on which it received the polling message.
Connections that are not required can be removed from the list of configured connections at
any time. Follow the steps outlined below:
1. Select the connection in the "Configured connections" window.
2. Select the "Edit" > "Delete" menu.
or
Select the "Delete" menu in the displayed shortcut menu (right mouse button).
Bad connections displayed in the configured connections window are shown in red and can
result from bad configuration or subsequent changes to a configuration. If there is an
incorrect connection between two subscribers, the old and no longer valid connection must
be deleted from the configured connections and the current connection must be taken from
the list of possible connections again.
Note
If a connection configured in the network configuration is not included in the list of possible
connections because it is invalid, this is displayed in the list of invalid connections. The
invalid connections dialog is described separately and contains information on connections
that do not conform.
Saving the connection configuration
Once any invalid connections have been checked and removed and all required connections
configured so that they appear in the left-hand window, the connection configuration must be
saved with the SINAUT / Save menu or the Save button in the toolbar. Saving is necessary
to store the connections permanently.
If a message is displayed during saving indicating that a connection between two stations
configured in NetPro could not be found, the connection must be checked in NetPro and
reconfigured.
After saving the connection configuration, open Subscriber Administration of the SINAUT
Configuration Tool to configure the subscriber data and to generate the system data blocks
there.
Changing the connection configuration
By opening the connection configuration again, you can change the scope of the configured
connections at any time. By changing parameter settings or by reconfiguring, it is possible
that a previously configured connection no longer exists. This then appears in the Recover
lost connections list that is described separately.
After changing the connection configuration, this must be saved, Subscriber Administration
must be called and the generation of the system data blocks started.
To document the configured DNP3 connections, the SINAUT configuration tool allows
connection lists to be printed in 2 formats. You start a printout with the
146
Project / Print
System Manual, 12/2015, C79000-G8976-C253-04
menu.