3. Select a second destination subscriber in the list box.
4. Transfer the parameters to this other destination subscriber using "Paste" in the shortcut
menu.
6.6.7

Objects of TD7onTIM

Transmission direction of the objects
The transmission direction of the objects can be seen in the name suffixes _S or _R (send or
receive):
● _S
send direction
– Use in the station type "station" for the monitoring direction (in)
– Use in the station type "master station" for the control direction (out)
● _R
Receive direction
– Use in the station type "station" for the control direction (out)
– Use in the station type "master station" for the monitoring direction (in)
Overview of the TD7onTIM objects
Table 6- 5
System object
General system objects
WatchDog
PartnerStatus
OpInputMonitor
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
Station sends message to master station.
Master station sends message to station.
Station receives message from master station.
Master station receives message from station.
System objects of TD7onTIM
Function
Monitoring of the CPU-TIM connection
Indicates to the CPU whether the communication between CPU and local
TIM is still working; in other words, whether TD7onTIM is still reading from
and writing to the memory areas of the CPU.
Displays the status of the connection with a maximum of 8 communications
partners
Signals to the CPU whether communication with a partner "DNP3 master
station" is functioning or disrupted.
Signals detection of hardware entries
Indicates the status of operator input to the CPU (with command, setpoint,
and parameter input).
Is not normally used with the DNP3 protocol.
The SINAUT Configuration Tool
6.6 TD7onTIM
177