Siemens SIMATIC TIM 3V-IE DNP3 System Manual page 22

Industrial remote communication telecontrol
Table of Contents

Advertisement

Uses and properties of the TIM
1.5 DNP3 device attributes of the TIM
Attribute
Meaning
217
Accuracy of the TIM time stamp
218
Time for which the time stamp accuracy can be
maintained following synchronization.
219
Support of analog output events
220
Max. index of the analog outputs
221
Number of analog outputs
222
Support of binary output events
223
Max. index of the binary outputs
224
Number of binary outputs
225
Support of frozen counter events
226
Support of frozen counters
227
Support of counter events
228
Max. index of the counters
229
Number of counters
230
Support of frozen analog inputs
231
Support of analog inputs
232
Max. index of the analog inputs
233
Number of analog inputs
234
Support of double bit inputs
235
Max. index of double bit inputs
236
Number of double bit inputs
237
Support of event messages with binary inputs
238
Max. index of the binary inputs
239
Number of binary inputs
240
Max. size of the application layer fragments in send
direction (station → master station)
241
Max. size of the application layer fragments in re-
ceive direction (master station → station)
242
TIM software version
243
TIM hardware version
244
Not defined in the protocol specification
245
User-specified string (location)
246
User-specified string (code)
247
User-specified string (name)
248
Serial number of the TIM
249
DNP3 implementation level
250
Product name and model
252
Vendor
22
Return value of the DNP3 TIM
10 ms
600 s
Not supported (negative acknowledgment)
According to the configuration
Max. index +1
Not supported (negative acknowledgment)
According to the configuration
Max. index +1
Is supported
Is supported
Is supported
According to the configuration
Max. index +1
Not supported (negative acknowledgment)
Is supported
According to the configuration
Max. index +1
Not supported (negative acknowledgment)
0
0
Is supported
According to the configuration
Max. index +1
2048 bytes
2048 bytes
Software version
Hardware version
-
Not supported (negative acknowledgment)
MAC address as string
Not supported (negative acknowledgment)
Not supported (negative acknowledgment)
Value of the configured conformity level of the DNP3
master station
Order number as string
SIEMENS AG
System Manual, 12/2015, C79000-G8976-C253-04
TIM DNP3