Parameter Window Output - ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.2.11
Parameter window
Output
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
In this parameter window all settings for the Output are undertaken.
Reaction of output
Options:
Normally closed contact
normally opened contact
You can be set in this parameter whether the output operates as a Normally
closed contact or Normally open contact.
Normally opened contact: An ON telegram (1) closes the contact and
an OFF telegram (0) opens the contact.
Normally closed contact: An ON telegram (1) opens the contact and
an OFF telegram (0) closes the contact.
Contact position on bus voltage failure
Options:
opened
closed
unchanged
The output can adopt a defined state on bus voltage failure using this
parameter.
opened: The contact is opened with bus voltage failure.
closed: The contact is closed with bus voltage failure.
unchanged: No change of the contact position.
Note
The reaction on bus voltage failure, recovery and download is to be
monitored.