ABB i-bus KNX FCA/S 1.1M Product Manual page 45

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Meaning
Options:
current fan speed
required fan speed
This parameter defines whether the status of the current fan speed
or the required fan speed is displayed.
Note
The limitations are included in this observation, i.e. if a limitation
allows only fan speed 2 and the fan is operating at fan speed 2,
and for example, a telegram to switch up is received, the required
fan speed remains at 2 as fan speed 3 cannot be achieved due to
the limitation.
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Enable communication object
"Status byte mode" 1 byte
Options:
no
yes
yes: The communication object Status byte mode is enabled.
From this status byte the states HEATING, COOLING, automatic, forced
operation and the four limitations are indicated directly via a 1 bit coding.
For further information see:
With the option yes two further parameters appear:
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Status byte, Forced
operation, page 157
43