Commissioning
Limitation on forced operation
Options:
3, 2, 1, OFF
unchanged
OFF
1
1, OFF
2
2, 1
2, 1, OFF
3
3, 2
3, 2, 1
This parameter sets which fan speed is set with active forced
operation or that may not be exceeded or undershot.
3, 2, 1, OFF: Everything is possible.
Unchanged: The state is retained.
OFF: Off.
1: limited to speed 1.*
1, OFF limited to speed 1 and off.
2: limited to speed 2.*
2, 1: limited to speed 2 and 1.
2, 1, OFF: limited to speed 2, 1 and off.
3: limited to speed 3.*
3, 2: limited to speed 3 and 2.
3, 2, 1: limited to speed 3, 2 and 1.
* The control value is ignored.
Enable automatic operation
Options:
no
yes
yes: Automatic operation is enabled. Furthermore the parameter
window
Automatic
operation, on page 46 appears.
Enable direct operation
Options:
no
yes
yes: Direct operation is enabled. Furthermore the parameter window
Direct
operation, on page 52 appears.
38