ABB i-bus KNX FCA/S 1.1M Product Manual page 27

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Valve HEATING
Options:
enabled
disabled
With this parameter the button can be enabled or disabled.
Enabled: The button is enabled.
Disabled: The button is disabled.
Note
By pressing the Valve HEATING button
is controlled.
The indicator LED HEATING indicates the same value as the 1 bit status
of the valve control:
0 = LED HEATING off/Valve position equal to zero
1 = LED HEATING on/Valve position equal to zero
With a state change the new state is immediately indicated.
Function with manual operation
A target position which may not have yet been achieved is
approached. The first button push switches the target position to 0 %
if it was unequal to 0 % beforehand, and 100 % if it was unequal to
100 % beforehand. Thereafter, each push of a button toggles the
target position between 0 % and 100 %. During deactivation of
manual operation the target position is approached that would have
been set without manual operation.
With manual operation a set characteristic curve correction is not
taken into consideration.
Button function at overload
The description concerns the button HEATING
HEATING .
The device is in the KNX operating state and the output of the
HEATING valve has a malfunction, e.g. due to an overload.
The valve HEATING LED flashes with a frequency of five hertz to
indicate the malfunction. At the same time the communication object
Overload Valve HEATING sends the value 1. With the respective
valve HEATING button the fault is acknowledged and the
communication object Overload Valve HEATING is reset to the value
0. In order to acknowledge the fault with the valve HEATING button,
the button must be pressed for longer than four seconds.
If the fault continues to persist after acknowledgement, the valve
HEATING button indicates it by flashing (five hertz). The communication
object Overload Valve HEATING is set again to the value 1.
Note
If the device is in Manual operation the acknowledgement function
Overload is not available.
the connected valve
and the LED
25

Advertisement

Table of Contents
loading

Table of Contents