Parameter Window - Function - ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.2.7.2
Parameter window
- Function
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Various communication objects can be enabled in the parameter window -
Function.
Enable communication object
"Block" 1 bit
Options:
no
yes
yes: The 1 bit communication object Block is enabled and can then be
used for blocking.
With option yes the following parameters appear:
Disable on object value
Options:
1
0
Here you set the object value used to block the valve.
Enable communication object
"Forced operation" 1 bit
Options:
no
yes
yes: The 1 bit communication object Forced operation is enabled and
can then be used for forced operation.
Note
The characteristic curve adjustment is also active with forced operation.