ABB i-bus KNX FCA/S 1.1M Product Manual page 107

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
16
Status fan speed
The communication object is enabled if in parameter window Status messages the
parameter Enable communication object "Status fan speed" 1 byte is selected with option
yes.
You can parameterise whether only the communication object value is updated or if they are
only sent on the bus after a change or on request. It is possible to parameterise if the actual
or required speed are displayed with the status object.
With this communication object it is possible for example to display the fan speed on the
display as a direct figure value.
The following telegram values apply for the 1 byte object:
Figure value
Hexadecimal
0
00
1
01
2
02
3
03
17
Status fan speed 1
The communication object is enabled if in parameter window Status messages the
parameter Enable communication object "Status fan speed x" 1 bit is selected with option
yes.
It is possible to parameterise if a communication object value is only updated and not sent,
sent on request, or only sent when changed.
Furthermore, you can parameterise if the status should indicate a current fan speed or
a required fan speed.
With this communication object is possible to display the fan speed in a visualisation or
to indicate it on a display.
Telegram value:
0 = fan speed OFF
1 = fan speed ON
18
Status fan speed 2
See communication object 17
19
Status fan speed 3
See communication object 17
20
Not assigned.
Object name
Data type
no EIS, 1 byte
Fan
DPT 5.010
Binary value bit
Fan speed
76543210
00000000
0 (OFF)
00000001
Fan speed 1
00000010
Fan speed 2
00000011
Fan speed 3
EIS 1, 1 bit
Fan
DPT 1.001
Flags
C, R, T
C, R, T