Commissioning
No.
Function
47
Disable function time
This communication object is visible if in parameter window Output General the option yes
has been selected in the Enable staircase lighting time parameter. The staircase lighting time
can be enabled or disabled via this communication object.
After bus voltage recovery, the communication object value with the parameter Value object
"Disable function Time" on bus voltage recovery can be determined in the parameter window
Output staircase lighting time.
With a disabled function Time 1, the output can only be switched on or off, the staircase
lighting time function will not be triggered.
Telegram value
1 = staircase light disabled
0 = staircase light enabled
The contact position at the time of disabling and enabling is retained and will only be
changed with the next switch command to the communication object Switch.
48
Change duration of
staircase lighting
This communication object is visible if in the parameter window - Time the parameter Enable
communication object "Change duration of staircase lighting" 2 byte has been selected with
yes.
The staircase lighting time can changed via the bus using this communication object.
The time is defined in seconds.
The staircase lightning time which has already commenced is completed. A change of the
staircase lighting time is used the next time it is accessed.
With bus voltage failure the changed staircase lighting time is retained. Only after a complete
download of the application program, a version change, when the device has been
discharged or with an ETS reset, is the staircase lighting time duration overwritten with
the value set in the parameters.
49
Status switch
In the parameter window Output you can parameterise whether the communication object
value no, update only, after a change or after request is sent on the bus.
The communication object value directly indicates the current contact position of the
switching relay.
The status value can be inverted.
Telegram value
1 = relay ON or OFF depending on the parameterisation
0 = relay OFF or ON depending on the parameterisation
Object name
Data type
EIS 1, 1 bit
Output
DPT 1.003
EIS 10, 2 byte
Output
DPT 7.005
EIS 1, 1 bit
Output
DPT 1.001
Flags
C, W
C, R, W
C, R, T