With Switching Object - ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.3.3.4
Communication objects
HVAC System
2 Control values/2-pipe,

with switching object

© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
30
Control value, HEATING
The communication object is enabled if in parameter window Control input the parameter
HVAC System has been selected with the option 2 Control values/2-pipe, with switching
object.
Using this communication object the control value HEATING is predefined as a 1 byte %
value.
Telegram value:
100 % = ON, largest control value, maximum heating
31
Control value, COOLING
The communication object is enabled if in parameter window Control input the parameter
HVAC System has been selected with the option 2 Control values/2-pipe, with switching
object.
Using this communication object the control value COOLING is predefined as a 1 byte %
value.
Telegram value:
100 % = ON, largest control value, maximum cooling
32
Toggle,
HEATING/COOLING
The communication object is enabled if in parameter window Control input the parameter
HVAC System has been selected with the option 2 Control values/2-pipe, with switching
object.
If the value 1 is set in the parameter:
Telegram value:
0 = COOLING activated
1 = HEATING activated
If the value 0 is set in the parameter:
Telegram value:
0 = HEATING activated
1 = COOLING activated
Note
If communication object 32 Toggle HEATING/COOLING – Control input
receives a value, the monitoring time is started.
Object name
Control input
0 % = OFF, no heating
Control input
0 % = OFF, no cooling
Control input
Data type
Flags
EIS 6, 1 byte
C, W
DPT 5.001
EIS 6, 1 byte
C, W
DPT 5.001
EIS 1, 1 bit
C, W
DPT 1.1000