ABB i-bus KNX
3.2.2
Parameter window
Manual
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
In the parameter window Manual, all the settings for manual operation can
be made.
Function of manual operation
After connection to the bus the device is in KNX mode. The LED is off.
All LEDs indicate the actual input state. The respective Buttons are non-
functional. It is possible to switch between Manual operation and
KNX operation by pressing the
If manual operation is activated, the current fan speed remains set and
can only be operated manually. Here any limitations, forced operations and
programmed dwell times are not considered.
If manual operation is deactivated, the fan sets to a speed to which it would
also be set without manual operation, e.g. via the value of the
communication objects.
The setting occurs with the parameterised dwell times!
Switch on of manual operation:
Press button
until the yellow LED lights continuously.
Switch off of manual operation:
Press button
until LED no longer lights.
Note
If button
is released again before two seconds have elapsed, the LED
reverts to its old state and there is no reaction.
If manual operation is disabled via the application program, there is no
reaction and the device remains in the KNX operation state. If it has been
disabled, LED is switched on or over after it has flashed for three
seconds.
button.
22