Parameter Window - Status Messages - ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.2.4.1
Parameter window
- Status messages
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
The Status messages are defined in this parameter window.
Enable communication object
"Status speed x" 1 bit
Options:
no
yes
yes: Three 1 bit communication objects, Status fan speed x,
x = 1 to 3 are enabled.
The setting of a fan speed is displayed via these communication objects.
You can parameterise if the status of a current fan speed or a required
fan speed are displayed.
With option yes the following parameters appear:
Meaning
Options:
current fan speed
required fan speed
This parameter defines whether the status of the current fan speed
or the required fan speed is displayed.
What is the current fan speed?
The current fan speed is the speed at which the fan is actually
operating.
41