Commissioning
Function time on ON
Options:
none
switching delay
minimum time
The function Time at fan ON is defined with this.
none: No time function is executed.
switching delay: The fan is switched on using this delay.
minimum time: The fan remains ON for at least this time.
With option switching delay the following parameters appear:
Time in s [1...65,535 x 0.1]
Options:
1...20...65,535
The fan is switched on using this delay.
With option minimum time the following parameters appear:
Time in s [1...65,535]
Options:
The fan remains ON for at least this time.
Function time on OFF
Options:
none
switching delay
minimum time
The function Time at fan OFF is defined with this.
none: No Time function is executed.
switching delay: The fan is switched off using this delay.
minimum time: The fan remains OFF for at least this time.
With option switching delay the following parameters appear:
Time in s [1...65,535 x 0.1]
Options:
The fan is switched off using this delay.
With option minimum time the following parameters appear:
Time in s [1...65,535]
Options:
1...20...65,535
The fan remains OFF for at least this time.
1...20...65,535
1...20...65,535