Commissioning
No.
Function
21
Limitation 1
The communication object is enabled if in parameter window Automatic operation the
parameter Enable limitations has been selected with the option yes.
The limitation 1 is active if a telegram with the value 1 is received on the communication
object Limitation 1 The Limitation 1 is deactivated if a telegram with the value 0 is received
on the communication object Limitation 1
When Limitation 1 is activated, the fan can only assume the set fan speed or fan speed
range in the parameter window Fan B Limitation. The valve position is independently
programmable from the fan limitation.
Telegram value:
0 = limitation x inactive
1 = limitation x active
22
Limitation 2
See communication object 21
23
Limitation 3
See communication object 21
24
Limitation 4
See communication object 21
Object name
Data type
EIS 1, 1 bit
Fan
DPT 1.003
Flags
C, W
106