Parameter Window "Output - ABB i-bus EIB/KNX AA/S 4.1 Product Manual

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
4.2.2
Parameter window
"Output X 1/2"
Commissioning
Fig. 8: Parameter window "Output X 1/2"
Input format
Options:
– 16 Bit
– 8 Bit
Different communication objects are displayed for the input values and the
status output dependent on this parameter.
8-bit: In 8-bit mode the output features a 1-bit object and a 4-bit object.
The input value range (0 or 255) is defined in this mode. The function of the
output corresponds in this case with the EIB / KNX standard for dimming
actuators.
If the 8-bit mode is set the parameter "Time between 2 of 255 dimming
steps" and "Response on reception of value" is displayed on the
Output X 2/2 parameter window (see 4.2.3).
Input value for 0 % output value
Input value for 100 % output value
Options:
– 32768...32767 (0 or 1000)
For setting the input value range for 0 % or 100 % output value with 16-bit
input format.
If the 8-bit mode has been selected with the "Input format" parameter,
the input value range is determined:
Input value for 0 % output value
Input value for 100 % output value 255
The function of the output corresponds in this case with the EIB / KNX
standard for dimming actuators.