ABB i-bus KNX FCA/S 1.1M Product Manual page 25

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Manual operation
Options:
enable/disable via communication object
enabled
disabled
This parameter defines if the switch over between the operating states
manual operation and KNX operation is enabled or disabled via the button
on the device.
enable/disable via communication object: The communication object
Enable/block manual operation – Manual operation appears.
Telegram value
0 = enable button
1 = disable button
Note
The manual operation overwrites the input states.
Reset manual operation to KNX operation
Options:
no
after 1/3/10/30 minute(s)
This parameter determines how long the Fan Coil Actuator remains in the
Manual operation mode after pressing the
no: The Fan Coil Actuator remains in Manual operation until the button
is pressed again.
after X minutes: The Fan Coil Actuator remains in Manual operation
after the last button push until either button
programmed time has timed out.
Enable communication object "Status man. operation" 1 bit
Options:
no
yes
yes: An additional parameter appears:
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent (it can be read
via the communication object).
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or
a request.
button.
is pushed again or the
23