Commissioning
Enable communication object
"Status switch" 1 bit
Options:
no
yes
yes: Further parameters are visible:
Send object value
(Object "Status switch")
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Object value of contact position
(Object "Status Switch")
Options:
1=closed, 0=open
0=closed, 1=open
With this parameter the communication object value of the switch
status (Status Switch) is defined.
1=closed, 0=open: A closed contact is represented by
communication object value 1 and an open contact is represented
by the value 0.
0=closed, 1=open: A closed contact is represented by
communication object value 0 and an open contact is represented
by the value 1.
Note
The contact position, and thus the switch status can result from a series
of priorities and links.