ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
38
Status valve purge
The status of the valve purge is visible via this communication object.
Telegram value:
0 = valve purge not active
1 = valve purge active
Note
The status is displayed as soon as a purge has been activated. The status
remains active even when the purge has been interrupted, e.g. by a priority.
39
Status valve position
This communication object is visible if in parameter window Valve HEATING in the Function
parameter window, the parameter option 1 bit has been selected for Enable communication
object "Valve position status".
The status of the valve position is visible via this communication object.
Hereby, the target position where the valve should move to is always transferred.
The display LED HEATING ( ) indicates the same value as the status.
Telegram value:
0 = Valve position equal to zero/LED HEATING off
1 = Valve position not equal to zero/LED HEATING on
39
Status valve position
This communication object is visible if in parameter window Valve HEATING in the Function
parameter window, the parameter option 1 byte has been selected for Enable
communication object "Valve position status".
The status of the valve position is visible via this communication object.
Hereby, the target position where the valve should move to is always transferred.
Die Anzeige LED HEIZEN ( ) zeigt den gleichen Wert wie der Status an.
Telegram value:
0...255 = valve position is displayed directly as a figure value
At 0 = LED HEATING off
At > 0 = LED HEATING on
Object name
Data type
EIS 1, 1 bit
Valve HEATING
DPT 1.003
EIS 1, 1 bit
Valve HEATING
DPT 1.001
EIS 5, 1 byte
Valve HEATING
DPT 5.001
Flags
C, R, T
C, R, T
C, R, T