Commissioning
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Enable valve purge
Options:
no
yes
yes: The 1 bit Trigger valve purge communication object is enabled.
Note
If the valve purge is interrupted by a higher priority, it will restart after the
completion of the priority task, unless, i.e. the control value was 100 % or
it was active for the duration of the purge time due to the higher priority.
The valve position for purging is always the control value 100 %.
A correspondingly matched curve is considered.
For further information see:
With option yes the following parameters are visible:
Enable communication object
"Status valve purge" 1 bit
Options:
no
yes
yes: The 1 bit Status valve purge communication object is enabled.
The status of the valve purge and the following additional parameters
are visible via this communication object.
Priorities,
with, page 153