ABB i-bus KNX FCA/S 1.1M Product Manual page 84

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Cyclic sending of object
"Switch" communication object
Options:
no
yes
yes: The following parameters are visible:
on object value
Options:
1
0
0 or 1
1: The object value is sent cyclically with 1.
0: The object value is sent cyclically with 0.
0 or 1: The communication object is sent cyclically.
What is cyclic sending?
Cyclic sending enables the communication object "Switch"
to send automatically at a fixed interval.
If cyclic sending is only carried out for a specific object value
(ON or OFF), this condition refers to the value of the
communication object. It is therefore possible in principle to start
cyclic sending by sending a value to the communication object
Switch. As this behaviour is generally unwanted, the flags Write
and Update of the communication object are deleted in the
preliminary setting so that they cannot be changed via the bus.
If this functionality is still required however, these flags should
be set accordingly.
With changes to the Switch communication object and after bus
recovery changes (after the send delay time has elapsed),
the object value is sent immediately on the bus and the
transmission cycle time restarts.
Telegram repeated in s [1...65,535]
Options:
1...60...65,535
The send cycle time describes the time used between two cyclically
sent telegrams.
Activate minimum signal time
with rising edge
Options:
no
yes
yes: The following parameter is visible:
in value x 0.1 s [1...65,535]
Options:
1...65,535
82