Commissioning
With option yes the following parameters appear:
Forced operation on object value
Options:
1
0
Here you set the object value used to forcibly operate the valve.
Valve position on forced operation in %
[0...100]
Options:
0...30...100
Here the forced operation of the valve position in percent is set.
Note
The characteristic curve adjustment is active with forced operation.
Enable communication object
"Status valve position"
Options:
no
1 bit
1 byte
Note
The valve position status is sent immediately after the control value is
received.
1 bit: The following parameters appear:
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Object value with valve position > 0
Options:
1
0
1 byte: The following parameter appears:
72