ABB i-bus KNX FCA/S 1.1M Product Manual page 102

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.3.3.5
Communication objects
HVAC System
2 Control values/4-pipe
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
30
Control value, HEATING
The communication object is enabled if in parameter window Control input the parameter
HVAC System has been selected with the option 2 Control values/2-pipe.
Using this communication object the control value HEATING is predefined as a 1 byte %
value.
Telegram value:
100 % = ON, largest control value, maximum heating
31
Control value, COOLING
The communication object is enabled if in parameter window Control input the parameter
HVAC System has been selected with the option 2 Control values/2-pipe.
Using this communication object the control value COOLING is predefined as a 1 byte %
value.
Telegram value:
100 % = ON, largest control value, maximum cooling
32
Not assigned.
Object name
Control input
0 % = OFF, no heating
Control input
0 % = OFF, no cooling
Data type
Flags
EIS 6, 1 byte
C, W
DPT 5.001
EIS 6, 1 byte
C, W
DPT 5.001
100