Parameter Window B: Output - ABB i-bus KNX FCL/S 1.6.1.1 Product Manual

Blower actuator, fcl/s x.6.1.1 series
Table of Contents

Advertisement

®
ABB i-bus
KNX
Start-up
3.2.2.4

Parameter window B: Output

Note
All of the following descriptions and operating options apply to both the FCL/S 1.6.1.1 1-fold Blower
Actuator and the FCL/S 2.6.1.1 2-fold Blower Actuator.
All settings for output B are made in the B: Output parameter window.
These explanations also apply to outputs C, D, E if the parameter Outputs C, D, E in
Enable outputs
The explanations also apply for output F.
Outputs B...F must first be individually enabled in
Reaction of output
Options:
This parameter sets whether the output operates as a normally closed contact or normally open contact.
Normally opened contact: An ON telegram (1) closes the contact, and an OFF telegram (0) opens the
contact.
Normally closed contact: An ON telegram (1) opens the contact, and an OFF telegram (0) closes the
contact.
Contact position
on bus voltage failure
Options:
This parameter determines the response of the output on bus voltage failure.
Normally closed: The output is OFF.
Normally open: The output is ON.
Unchanged: The output retains the last state before bus voltage failure.
A...F, p.20 is set to Enable as switch actuators.
Normally opened contact
Normally closed contact
Normally closed
Normally Open
Unchanged
Parameter window Enable outputs
FCL/S x.6.1.1 | 2CDC508116D0203 55
Parameter window