Commissioning
Caution
The FCA/S 1.1M is supplied ex-works with a default setting (factory
default). This ensures the fan setting is switched off when the bus voltage
is applied to the relay for the first time. Thus, damage to the device due to
unintentional switch on during transport, e.g. due to vibration, is avoided.
It is advisable to apply a bus voltage before connecting the fan in order to
achieve a defined switch state of the fan.
This eliminates the possibility of the destruction of the fan due to an
incorrect contact setting.
Enable communication object
"Forced operation" 1 bit
Options:
no
yes
Through forced operation for example, a recirculation: valve OFF and
fan ON can be implemented.
yes: A 1 bit Forced operation communication object is enabled.
Further parameters appear at the same time:
Forced operation on object value
Options:
1
0
1: Forced operation is activated by a telegram with value 1.
0: Forced operation is activated by a telegram with value 0.
Note
During forced operation the settings set in Automatic operation are
ignored. Automatic operation is updated after forced operation has
been rescinded.
Important
Forced operation remains active until:
- the complementary set values are sent.
- the assignment is changed.
- the fan type is changed.
The forced operation is not deactivated, by a download of the
application program in which the fan type and the respective group
addresses are retained.
The forced operation is reset if an ETS reset has occurred.
37