ABB i-bus KNX FCA/S 1.1M Product Manual page 22

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Rate of telegrams
Options:
not limited
1/2/3/5/10/20 telegrams/second
0.05/0.1/0.2/0.3/0.5 seconds/telegram
A telegram limitation is implemented to control the bus load created
by the device.
Send communication object "In operation"
Options:
no
yes
The in operation communication object indicates the correct function of the
device on the bus. This cyclic telegram can be monitored by an external
device.
Note
After bus voltage recovery the communication object is sent after the set
sending and switching delay.
yes: Additional parameters appear:
Telegram repeated in s [1...65,535]
Options:
1...60...65,535
Here the time interval at which the In operation communication object
cyclically sends a telegram is set.
Send value cyclically
Options:
0
1
The setting defines the value that the communication object sends
on the bus.
Enable input A
(binary input, contact scanning)
Enable input B
(binary input, contact scanning)
Options:
no
yes
yes: The input is activated. A further parameter window is provided
on the left half of the window.
Note
The inputs are equipped as binary inputs with contact scanning.
The scanning voltage is provided by the device.