Output - ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.3.10

Output

© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
No.
Function
45
Switch
This communication object is used for switching of the output ON/OFF.
The device receives a switch command via the switch object.
Normally opened contact:
Telegram value
1 = switch ON
0 = switch OFF
Normally closed contact:
Telegram value
1 = switch OFF
0 = switch ON
46
Permanent ON
With this communication object the output can be forcibly switched on.
If the communication object is assigned with the value 1, the output is switched on
irrespective of the value of the object Switch and remains switched on until the
communication object Permanent ON has the value 0. After ending the permanent ON state,
the state of the communication object Switch is used.
Permanent ON only switches ON and "masks" the other functions. This means that the other
functions, e.g. staircase lighting time, continue to run in the background but do not initiate
a switching action. After the end of permanent ON the switching state which would result
without the permanent ON function becomes active. The behaviour for the function staircase
lighting after permanent ON is programmed in parameter window
This communication object can be used for example to allow the service or maintenance and
cleaning personnel to initiate a permanent ON. The device receives a switch telegram via the
switch object.
Permanent On becomes inactive after a download or bus voltage recovery.
Telegram value
1 = activates Permanent ON
0 = deactivates Permanent ON
Object name
Data type
EIS 1, 1 bit
Output
DPT 1.001
EIS 1, 1 bit
Output
DPT 1.003
-
Time, page 90.
Flags
C, W
C, W
119