Commissioning
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change
or a request.
Note
The status is sent immediately as soon as a new control value is
received.
Duration of valve purge
in min. [1...255]
Options:
1...10...255
The time duration for the valve purge is set with this parameter. In this
time the valve is fully opened. When the time has elapsed, the state
before the purge is re-established.
Note
The opening time of the valve must be considered when entering
the purge time.
The characteristic curve adjustment is active for the valve purging
time.
Automatic valve purge
Options:
no
yes
yes: The following parameters appear:
Purge cycle in weeks
[1...12]
Options:
1...6...12
The counter for automatic purging starts to run when the
parameter is downloaded. The time is reset each time it is
downloaded.
The time is reset as soon as purging is completed.
This can occur either through automatic purging or
via the communication object Trigger valve purge.