ABB i-bus KNX
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
Valve COOLING
The operation of the COOLING valve does not differ from the operation
of the HEATING valve.
For further information see: Parameter description
Input A
Options:
Block
Switch
Button
With this parameter the button can be disabled, or programmed as a switch
or push button.
Block: The button is disabled.
Switch: With every actuation the states of the input and the LED are
changed.
Push buttons: Press button => input closed, LED on
Release button => input opened, LED off
Note
By pressing button
binary input A is simulated.
The display indicates the current input state. The parameterised features
are executed.
Input B
The operation of input A does not differ from the operation of input B.
Output
Options:
enabled
disabled
With this parameter the button can be enabled or disabled.
enabled: The button is enabled.
disabled: The button is disabled.
Note
By pressing the button
The display
indicates the contact state.
LED on = contact closed
LED off = contact opened
Valve
the relay is toggled.
HEATING, page 65
26