1918
Module 9100 Assign data interface
With Module 9100 you assign an interface to the PLC and specify the transfer
parameters. They initialize the interface, thereby erasing any errors that may
have occurred. The interface is then ready to receive.
Once assigned to the PLC, the interface is disabled for use by the input/output
program of the user interface. The assignment is canceled when the PLC
program is recompiled.
Can only be called in a submit job or spawn job!
Call:
PS
B/W/D/K <>Interface>
0: RS232
1: RS422
PS
B/W/D/K <>Transfer parameters>
0: From MP50x0.2
1: From MOD function
2: From MP50x0.3
CM
9100
Error code:
Marker
Value
Meaning
M4203
0
Interface was assigned
1
Error code in W1022
W1022
1
Incorrect interface or incorrect transfer parameter
13
No connection
14
Interface busy or input/output not ready
17
Incorrect data transfer rate
20
Module was not called in a spawn job or submit job
HEIDENHAIN Technical Manual iTNC 530 HSCI