Network connections for LSV2 applications are cyclically checked. If the
remote station does no longer respond (e.g. because the connecting cable
was disconnected), the LSV2 connection will automatically be terminated. In
the default setting, the connection is checked four times within a ten-second
cycle. If the remote station does not respond after the fourth attempt, the
connection is automatically terminated.
If you do not want a cycle of ten seconds, you can increase the cycle time to
a maximum of 6000 seconds with the REMOTE.TIMEKEEPIDLE token.
Input example: REMOTE.TIMEKEEPIDLE = 250
Indicate a specific pocket table. If this token exists in OEM.SYS, files of the
type *.tch are not displayed in the file manager and in the machining modes.
Only for remote diagnosis with the TeleService PC software:
Path of a text file containing the content of the UDP service request package,
with which the machine can be identified uniquely. The iTNC reports this
content to the TSAgent when the SERVICE soft key is pressed. With short
texts it can also be entered directly in quotation marks. If this entry is missing,
then the default value PLC:\REQUEST.SYS is used automatically.
Input example: SERVICE.REQUEST.CONTENT = PLC:\REQUEST.SYS
Only for remote diagnosis with the TeleService PC software:
IP address of the PC that receives the service request.
Input example: SERVICE.REQUEST.HOST = 160.1.180.99
Only for remote diagnosis with the TeleService PC software:
Repeat time in seconds for the UDP packets. If this entry is missing, then the
default value 10 is used automatically.
Input example: SERVICE.REQUEST.PERIOD = 10
Only for remote diagnosis with the TeleService PC software:
Port for the UDP packets. If this entry is missing, then the default value 19001
is used automatically.
Input example: SERVICE.REQUEST.PORT = 19001
Only for remote diagnosis with the TeleService PC software:
Timeout checking interval in minutes—if there has been no data transfer over
the Ethernet since the last timeout check, transmission of the service
requests is terminated. If this entry is missing, then the default value 15 is
used automatically.
Input example: SERVICE.REQUEST.TIMEOUT = 15
Path for PLC soft-key project file *.spj with the structure of the vertical PLC
soft key.
Input example: SOFTKEYPROJECT = PLC:\SOFTKEY.SPJ